The nylon mesh filter consists of an aluminum alloy frame and nylon mesh, with internal support welded from iron wire or flat steel. It is washable and reusable, offering high economy. The filter has a simple, beautiful, and sturdy structure, commonly used in primary filtration of central air conditioning.
Shenzhen Mingyang Purification Technology Co., Ltd. Founded in 2008, we are a specialized enterprise integrating R&D, design, manufacturing, installation, and after-sales service of air filters and purification equipment. With 17 years of manufacturing experience, we are certified under ISO9001 and ISO14001. Our business covers electronics, food, pharmaceuticals, hospitals, aviation, and many other fields, committed to providing high-quality air purification solutions for customers.
Mingyang nylon mesh filter is aHigh airflow, low resistance, reusable through cleaningThe core product for primary air filtration, designed for the pre-filtration stage of various ventilation systems. The product consists of an aluminum alloy frame and polyamide nylon mesh, with internal support welded from iron wire or flat steel. The filter media is black nylon mesh, offering excellent acid and alkali resistance and corrosion resistance. It can be repeatedly cleaned without affecting filtration efficiency. The standard design features double-layer nylon mesh, but multi-layer structures can be customized as needed.
This product primarily filters airborne dust particles ≥5 μm, with a gravimetric filtration efficiency reaching G2 grade (60% gravimetric efficiency) and an initial resistance of only 25 Pa. It complies with the GB/T 14295-2019 standard for air filters and is an ideal primary filtration solution for central air conditioning, household air conditioning, and various large building ventilation systems. Non-standard specifications can also be customized to meet specific installation space, airflow requirements, and personalized filtration needs.
Suitable for primary filtration in central air conditioning and centralized ventilation systems of large commercial buildings such as office buildings, conference rooms, hospitals, shopping malls, stadiums, and airports, effectively intercepting airborne ≥5μm large particle dustHair, fibers, and other impurities, preventing subsequent high-efficiency filters from clogging prematurely, extending their service life by over 30%, and reducing overall maintenance costs. It can also be used for primary filtration in household air conditioners and fresh air systems to improve indoor air cleanliness.
Designed for special environments requiring acid and alkali resistance, it can be used as ventilation filters in chemical, electroplating, and pharmaceutical industries, as well as air conditioning filter equipment for clean room return air outlets. The corrosion-resistant properties of the nylon mesh ensure stable filtration performance in complex media environments, effectively intercepting large particles in corrosive gases and protecting downstream equipment.
As a pre-filtration stage for industries requiring basic air cleanliness, such as electronics, food, pharmaceuticals, hospitals, and aviation, it lays the foundation for subsequent medium and high-efficiency filtration processes. In electronics factories, it prevents dust from contaminating precision components; in food processing plants, it reduces the impact of airborne impurities on product hygiene; in hospitals, it lowers the risk of particle transmission in ventilation systems, fully adapting to diverse industry air purification needs.
| Project | Detailed Specifications |
|---|---|
| Product Name | Nylon mesh filter |
| Brand | Mingyang |
| Frame Material | Aluminum Alloy Profile |
| Frame Thickness | 8, 10, 21, 46mm (customizable) |
| Filter Media Type | Polyamide nylon mesh (black) |
| filtration principle | Air Pressurization Adsorption Method |
| Gravimetric Efficiency | G2 (60% weight method) |
| Structure Type | Panel type, single or double layer nylon mesh (multi-layer customizable) |
| Internal support | Iron wire or flat steel welded support |
| Applicable Filtration Target | Air purification, mainly filtering dust particles ≥5μm |
| Initial resistance at rated airflow | 25Pa (compliant with GB/T 14295-2019 standard) |
| Product features | High airflow, low resistance, washable, acid and alkali resistant, corrosion resistant, reusable |
| Quality Standards Implemented | GB/T 14295-2019 |
| Application Fields | Electronics, food, pharmaceuticals, hospitals, aviation, commercial buildings, chemical industry, etc. |
| Dimensions (mm) | Rated airflow (m³/h) | Initial Resistance (Pa) | Efficiency class | Filter media model | Frame thickness optional (mm) |
|---|---|---|---|---|---|
| 295×295×10/21 | 800 | 25 | G2 | Single or double layer nylon mesh | 8、10、21、46 |
| 495×295×10/21 | 1500 | 25 | G2 | Single or double layer nylon mesh | 8、10、21、46 |
| 495×495×10/21 | 2500 | 25 | G2 | Single or double layer nylon mesh | 8、10、21、46 |
| 595×295×10/21 | 1800 | 25 | G2 | Single or double layer nylon mesh | 8、10、21、46 |
| 595×495×10/21 | 3000 | 25 | G2 | Single or double layer nylon mesh | 8、10、21、46 |
| 595×595×10/21 | 3600 | 25 | G2 | Single or double layer nylon mesh | 8、10、21、46 |
Note: The above are only some common specifications and models. Shenzhen Mingyang Purification Technology Co., Ltd. Custom non-standard nylon mesh filters can be tailored according to the customer's actual installation space, airflow requirements, and application scenarios. Custom products also comply with the GB/T 14295-2019 standard to ensure testing standards and performance. If the ambient temperature and humidity deviate from standard conditions (23°C, 50% RH), the resistance value must be corrected using the formula: Corrected resistance = Measured resistance × (Standard air density / Actual air density), where standard air density is 1.2 kg/m³.
Cleaning method: Use low-pressure clean water (water pressure ≤0.3 MPa) or compressed air (air pressure ≤0.4 MPa) to gently rinse along the fiber direction of the filter media. Avoid reverse rinsing to prevent damage. For stubborn stains, use a neutral detergent. After cleaning, let it air dry naturally (avoid direct sunlight or high-temperature drying) before reinstalling.
Cleaning frequency: For general scenarios, clean every 1-2 months; for industrial environments with high dust concentration, clean every 15-30 days; when the pressure difference across the filter reaches 50 Pa (twice the initial resistance), clean immediately. After 5-8 normal cleanings, if the filter media is damaged, deformed, or filtration efficiency significantly drops (below 50% gravimetric efficiency), replace with a new filter.
Key parameters for selection: ① Airflow matching: Choose a model with rated airflow matching the actual airflow of the ventilation system; it is recommended that actual airflow does not exceed 120% of rated airflow. ② Installation dimensions: Confirm the length, width, and thickness of the installation space, and select standard sizes or custom non-standard sizes. ③ Frame thickness: Choose thickness specifications such as 8, 10, 21, or 46 mm based on installation depth; greater thickness provides more structural stability. ④ Operating environment: For general scenarios, select single-layer or double-layer nylon mesh; for corrosive environments, confirm the corrosion resistance compatibility of the filter media; for high-dust scenarios, multi-layer structures can be customized.
Additionally, considering the protection needs of downstream filtration equipment, the nylon mesh filter serves as primary filtration, mainly intercepting large particles. If downstream equipment requires high-precision filtration, it is recommended to use a higher-efficiency primary filter in combination.
Acid and alkali resistance: Can withstand common weak acids (e.g., acetic acid, citric acid) and weak bases (e.g., sodium hydroxide, sodium carbonate) with a pH range of 4-10. Suitable for ventilation filtration in chemical, electroplating, and pharmaceutical industries. Not recommended for extreme environments with high concentrations of strong acids or bases (pH <4 or pH >10).
Service life: In general civil building ventilation scenarios, with regular cleaning, the service life is 8-12 months; in industrial dust environments, 4-8 months; in corrosive environments, 3-6 months. Service life is closely related to usage frequency and maintenance; proper cleaning and maintenance can effectively extend the service cycle.
Shenzhen Mingyang Purification Technology Co., Ltd. With 17 years of experience in air filter manufacturing, we are an ISO9001/14001 certified company, equipped with advanced automated production equipment and professional testing equipment. We adhere to the corporate philosophy of 'Treating others with sincerity, earning trust with integrity, ensuring quality, prioritizing reputation, and putting service first,' providing comprehensive service guarantees to customers.